Mode
Seven Modes of operation are available.
Six limits apply to all modes.
Target temperature is the center point of both adaptive and constant temperature bands.
Storage 1:
Recommended for USA cornbelt.
Fans run when:
Backlog is greater than zero.
-
Temperature is within the adaptive band.
-
EMC is within the adaptive band.
Storage 2:
Recommended for dry climates or if grain is dryer than TMC.
Same as Storage 1 except:
EMC band doesn’t expand on the dry side. Fixed at – 0.2%.
Storage 3:
Recommended for wet climates.
Same as Storage 1 except:
EMC band doesn’t expand on the wet side. Fixed at + 0.2%.
rewetting
Backlog is ignored.
Fans run when:
-
EMC is greater than the moisture setting.
-
Temperature is within the constant band. (Default is + 50°)
drying
Backlog is ignored.
Fans run when:
-
EMC is less than the moisture setting.
-
Temperature is within the constant band. (Default is + 50°)
Special 1:
Recommended for specific conditioning tasks, especially with high airflow available.
Backlog is ignored.
Fans run when:
-
Temperature is within the constant band. (Default is + 50°)
-
EMC is within the constant band. (Default is + .1%)
Special 2:
Same as Special 1 except:
Backlog is in effect.